Very Small Scale 0 ▲ Old Structures Engineering 1 hour ago · Tech · hide · 0 comments A lesson that structural engineers learn early on is to keep load paths as simple as possible, within the context of the architectural design. Here’s a bad load path: What you’re looking at: the white glazed brick veneer has been removed to expose the steel lintel. The mason was concerned, with good reason, that the unsupported brick above the lintel might shift, so they installed the upper, single 2×4 to carry load from the unsupported veneer to the lintel. And since the lintel end was later undermined by veneer removal, they added the lower, doubled 2×4 to carry load from the lintel down to the sill below. This is, as previously stated, a bad load path. The two pieces of shoring are not aligned, the veneer to the left of the removal area is being carried by a lintel that is temporarily shored at its end, rather than below the load. In other words, the load from the unsupported veneer goes through the upper shore, offsets through the lintel, and then through the lower shore to the… No comments yet. Log in to reply on the Fediverse. Comments will appear here.